The article preliminarily studies the structure of flexible interconnection system of MV distribution network, and understands the application scenario and equipment composition of the flexible system. For the purpose of reducing SOP loss, transformer loss and line loss, the operation of the MV flexible interconnected distribution network is optimized, the operation optimization model of the flexible interconnected distribution network is constructed, and the fault enumeration method is adopted as the reliability assessment method of the flexible interconnected system. Through experimental simulation, the stability, reliability and dynamic characteristics of the MV flexible interconnection system are explored respectively, and the system protection control strategy is proposed. For the same constant power load step, the larger the voltage loop proportional parameter is, the more stable the system tends to be, and the larger the voltage loop integral parameter and the station circuit parameter are, the more unstable the system tends to be. The maximum mutation value of the system constant power load gradually decreases when the station load power gradually increases. The reliability of the MV flexible interconnection system increases with the increase of SOP capacity. In the medium voltage flexible distribution interconnection system. The system damping, oscillation frequency and overshoot are significantly reduced and the peak time is increased when the DC voltage sag factor is increased.